| ControlRoomDesignConsideration |
|
|
|
| ControlRoom |
| Written by Administrator |
| Monday, 07 February 2011 14:27 |
|
Â
There are two major aspects of control room design that should be taken into account in the Initsys pre-installation Safety Design Report these are:
For industrial plants, control rooms are likely to be situated in separate buildings away from the process plant which they serve. For medium or small industrial control rooms may be within the building or control equipment may be located local to the control room. Whatever the location, control rooms should be designed to ensure that the risks to the occupants of the control room are within acceptable limits and that it is suitable for the purposes of maintaining control, should the emergency response plan require it, following any foreseeable, undesirable event within the control room environ. Events that may affect the control room are:
The threat from explosions and pressure bursts should be considered in the structural design of control building. A methodology for this is presented in the recent CIA/CISHEC guidance CIA Guidance for the location and design of occupied building on chemical manufacturing sites but this document is applicable in many cases. This considers the vulnerability of the building to possible overpressures associated with particular events. Buildings should be designed to withstand an overpressure that will ensure that risks to individuals within the building are below acceptable limits. Particular attention should be given to the provision of windows, the presence of heavy equipment on roofs (e.g. air conditioners) and the ability of internal fixtures to withstand the building shaking. If windows are present, consideration should be given to the use of laminated or polycarbonate glass, to prevent serious injury to occupiers of the control room in the event of an overpressure. ALARP (as low as reasonably practical) principles should be applied in these considerations and cost benefit used to determine if additional measures should be applied. In commerical control rooms consideration must be made for deliberate attack. In consideration of toxic gas releases the control room should provide a safe haven for its occupants. This will include arranging that the building is adequately sealed to prevent ingress of gases to levels of concentration that will affect the health and thereby the ability of the operators to maintain control. Careful consideration of the building ventilation system is required to ensure that air intakes are situated away from areas that may be affected or to arrange that there is no air intake during an incident, preferably by closure of an automatic valve linked to a gas analyser and or installation of a positive pressure environment. Suitable protection of building ventilation areas should be provided by CCTV and these linked to Merlin3's automatic environment alerting system. Measures for protection from fires should ensure the control room will withstand thermal radiation effects without collapse and that smoke ingress is controlled. Materials of construction should be fire resistant for the duration of any possible fire event. Smoke ingress may be controlled in a similar manner to toxic gas ingress. Each of these methodologies should be applied to control rooms within buildings as well as separate control buildings. Control panels and equipment cannot be so easily be protected, therefore diversity and redundancy should be applied to ensure that control can be maintained in an emergency. Risk Assessments should be undertaken to demonstrate that primary and secondary (domino) risks are within acceptable limits - have a backup plan and test it regularly. Human factors/ergonomicsOperators should be able to demonstrate that appropriate human factors considerations have been given to the design, commissioning, and operation of the control rooms under both normal and abnormal operating conditions to reduce the frequency of human error due to control room deficiencies. It is vitally important that a control room and its operators are considered as a whole system and not in isolation of each other. For example a well designed control room for use by 4 operators is dangerous when staffed by 3 operators. Similarly, the best-trained operators cannot guarantee high reliability in a poorly designed control room. Factors to be taken in account are included on the following paragraphs. Environmental issuesLayout
Maintenance
Thermal environment
Visual environmentLighting should be such that it does not create veiling reflections on VDUs or other reflective surfaces that require monitoring. The type of lighting should be adequate for the task. i.e. for office work a lux (lux is the unit of illuminance - measured using a light meter at the work surface) figure of between 500 - 800 is suggested. There should be no perceptible flicker from strip lighting. It is desirable to provide adjustable lighting for control rooms that are manned 24 hours a day. During night-time operation lighting is often dimmed. Windows in control rooms should not cause veiling reflections on reflective surfaces. Adequate means of blocking out direct sunlight should be provided. Auditory environmentThe average noise level within the control room shall not exceed 85 dB(A) during the length of the working day. For office work a noise level below 40 dB(A) is not desirable as it can cause interference between operators. Prolonged, very low or very high frequency noises should be avoided. Noise levels should not interfere with communications, warning signals, mental performance (i.e. be distracting). Merlin3 Man Machine Interface (MMI)For mental workload, conditions of over and under-arousal will be avoided. The duration of tasks that have an associated low or high level of mental workload will limited automatically with alerts to management if either are exceeded. Both these extremes will increase the likelihood of human error affecting the system. The design of the Initsys Merlin3 MMI is based on a full Task Analysis Before Intervention Plan. MerlinPHP and its associated SMS warning levels should be utilised to ensure that...... The interface will provide the operator with the general following information:
Control Room Alarms
Coding techniques
Designing displaysText
Labels
Display devices
|
| Last Updated on Monday, 07 February 2011 15:04 |